Whether a cable is buried underground, inside conduits, or exposed to open air affects its heat dissipation and current rating. 5. 3-Phase Cable Size Calculation Guide | PDF - Scribd

Vd per km for 10 mm² copper (from table) ≈ 3.8 V/A/km (3-phase) Vd = 3.8 × 51 × 0.15 = %Vd = 29.1 / 400 = 7.3% – exceeds 5% limit → increase size .

Electrical cable sizing is a balance between safety, efficiency, and cost. By rigorously calculating the load current, applying derating factors, checking voltage drop, and verifying short-circuit withstand capability, engineers ensure a reliable and safe electrical installation that will stand the test of time.

⚠️ This is a technical summary. Final cable sizing must consider local electrical codes, fault levels, correction factors for altitude, harmonics, and specific manufacturer data. Always consult a licensed electrical engineer for real installations.

Assume 4 mm² has a voltage drop of $11 \text mV/A/m$. $$V_d = \frac\sqrt3 \times 25.5 \times 50 \times 111000 = 24.3 \text Volts$$ Percentage drop = $(24.3 / 400) \times 100 = 6%$. Result: This exceeds the 5% limit. We must size up to 6 mm² .